Skip to main content

Jockey Pump Sizing and Options

Pressure maintenance pumps (PMP), or jockey pumps (JP) as they are more commonly referred to, are an often incorrectly sized part of a fire pump system. Lets walk through the fundamentals.

Why/When Required:

To start with, technically you are not required to provide a jockey pump on all systems.  NFPA 20 section A.4.25 states "Pressure maintenance (jockey or make-up) pumps should be used where it is desirable to maintain a uniform or relatively high pressure on the fire protection system."  The goal is to not shock the system with water hammer when the main fire pump starts. You don't want to be boosting the pressure from 10 psi to 150 psi. You want to be boosting the pressure in the 5-15 psi range.

It is our recommendation that in almost all situations, a jockey pump should be provided to minimize pressure surges when the main fire pump starts.

Jockey Pump Types:

Jockey pumps are not required to be listed per NFPA 20-2010 section 4.25.1.  The failure of a jockey pump results in the main fire pump which would be considered a success.

As such any type of commercial booster pump could be utilized.  However, as a practical matter there are three common types of pumps used.

Regenerative Turbine

Pro: Cheap Cost / Low HP

Con: High churn pressure - Even the smallest sizes have churn pressures in excess of 400 psi / Must use a pressure relief valve always / Low flow rates - do note expect to fill a large system quickly with these pumps

(Anvil Fire does not recommend this type due to ease of accidentally over pressurizing your system)

Vertical Multi-Stage

Pro: Very reliable / Can be selected to prevent exceeding system pressure ratings (i.e. 175 psi) / Ease of maintenance

Con: Slightly more expensive

(Anvil Fire includes this type in all our quotes)

Submersible Multi-Stage

If your water supply isn't pressurized (i.e. above-ground tank or city water supply) this is your only option. These are basically "well" pumps and will be submersed down into the water on the end of a 1.25 or 1.5 galvanized pipe.

Sizing of Jockey Pumps

Once you know what type of jockey pump you are using, you need to specify the size/rating. We don't recommend following the commonly referenced rule-of-thumb: a jockey pump at 1% of the rated capacity of the main fire pump.  It does not take into account the volume of your system and anticipated leakages. The sizing of the jockey pump, has very little to do with the size of your fire pump. Lets look at a couple system types and how we would size the jockey pumps.

GPM Rating - Aboveground Only Systems

For situations where the pressure maintenance pump serves only aboveground piping for fire sprinkler and standpipe systems, the pressure maintenance pump should be sized to provide a flow less than a single fire sprinkler. The main fire pump should start during any waterflow situation where a sprinkler has opened, which will not happen if the pressure maintenance pump is too large. 

NFPA 20-2016 section 4.26 states the pump "shall be sized to replenish the fire protection system pressure due to allowable leakage and normal drops in pressure". The appendix language goes on to state "... The main fire pump should start and run (providing a pump running signal) for any waterflow situation where a sprinkler has opened, which will not happen if the pressure maintenance pump is too large. "

One guideline that has been successfully used to size pressure maintenance pumps is to select a pump that will make up the allowable leakage rate in 10 minutes or 1 gpm (3.8 L/min), whichever is larger. From a practical standpoint, jockey pumps are "approximately" rated for 2.5 gpm or 5 gpm. We typically quote our pumps with a 5 gpm rated jockey pump.

GPM Rating - Large Underground Systems

Underground mains are permitted by NFPA 24, Standard for the Installation of Private Fire Service Mains and Their Appurtenances, to have some leakage.  

where:
L = testing allowance (makeup water), in gallons per hour
S = length of pipe tested, feet
D = nominal diameter of the pipe, in inches
P = average test pressure during the hydrostatic test, in pounds per square inch (gauge)
Assuming that you have a system that will not exceed 150 PSI in static pressure, the underground will need to be tested to 200 PSI.

So lets run the following example:
  • 500-feet of 6-inch Class 52 Ductile Underground (D = 6.280")
  • Hydrostatic test pressure of 200 psi
  • Allowable Leakage L = 0.30 gpm
Assuming you have a 2,000 gpm pump, do you really need a jockey pump rated for 20 gpm when the actual leakage should not exceed 0.30 gpm? We are back to our standard practice of a 5 gpm rated jockey pump being adequate unless you have a lot of underground.

PSI Rating - All Systems

Assuming we now know we are going to use a 5 gpm rated pump, what pressure (psi) rating should we select? There are two different design conditions we need to consider:
  1. Flow rate to keep up with expected system leakage
  2. Maximum expected churn (no-flow) pressure so as to not exceed system rated pressure
Since we know the expected system leakage is generally close to zero, we are mainly concerned with just making sure the jockey pump won't over pressurize the system. There are three different approaches we can take:
  1. Adjust controller setpoints so the jockey pump turns off (bad idea for a variety of reasons)
  2. Provide a pressure relief valve to accommodate over pressurization (subject to human error and potential mechanical failure)
  3. Select a pump with a churn pressure (+ suction pressure) that won't exceed you system rating
Guess what option Anvil Fire recommends? 

Jockey Pump Selection Table Summary

Anvil Fire represents AC Fire / Xylem products and generally follow the sizing chart below for jockey pumps. Reach out to your local regional rep and let us help you narrow down your options.






Popular posts from this blog

Installation of Diesel Fuel Tanks for Fire Pumps (OLD)

This article is based upon 2009 IFC codes and is obsolete. See newer version here:  https://blog.anvil-fire.com/2024/03/installation-of-diesel-fuel-tanks-for.html After you have determined the size of fuel tank you need for a diesel fire pump, what are the general requirements for installation?  Assuming that you are under under the International Building/Fire Codes, you would go through the following chain of code references: IFC (2009 edition) 3401.2 Nonapplicability. This chapter shall not apply to liquids as otherwise provided in other laws or regulations or chapters of this code, including: ... (3) Storage and use of fuel oil in tanks and containers connected to oil-burning equipment. Such storage and use shall be in accordance with Section 603 . For abandonment of fuel oil tanks, this chapter applies. IFC (2009 edition) 603.1 Installation. The installation of nonportable fuel gas appliances and systems shall comply the International Fuel Gas Code. The installation of all oth

Diesel Exhaust Requirements

The exhaust from a diesel engine driving a fire pump is an often-overlooked item.  The high heat put out by the exhaust is a hazard to occupants and can greatly contribute to overheating the room itself. NFPA 20 (2013 edition), section 11.5 covers "Engine Exhaust" and should be carefully reviewed. However as a starting point, the following items should be considered. Exhaust Discharge Location The first step is to determine where you are going to discharge the exhaust gases. NFPA 20 section 11.5.3 for "exhaust discharge location" has the generic common-sense requirements of do not discharge where you might hurt people, damage the building, or directed on combustible materials. But very little specific requirements are provided. There is a loose reference in NFPA 20 back to NFPA 37 ( Standard for the Installation and Use of Stationary Combustion Engines and Gas Turbines ). In addition, the International Mechanical Code (IMC) section 915.1 directs us back to NFPA 3

Fire Pump Rating (Size) Selection

Fire pump sizing is not like commercial pump sizing. We don't care about efficiency, and you order pumps in only specific sizes. This article touches upon some items to consider when picking a fire pump. In general, the first step is determining your system demand point. Discussion of how exactly you determine this is beyond the scope of this article and has a lot of nuance depending upon your site-specific needs. However, for simplicity let's assume that you have a dry-system in an attic with a demand point of 305 gpm (2535 sq ft x 0.10 gpm/sq ft x 1.20 overflow/imbalance factor). Rated Flow (gpm) Sizing The first item you must specify is the pump flow rate. Per NFPA 20 (2013 edition) table 4.8.2 pumps are only allowed to be listed with the following flow rates in gpm: 25, 50, 100, 150, 200, 250, 300, 400, 450, 500, 750, 1000, 1250, 1500, 2000, 2500, 3000, 3500, 4000, 4500, 5000 So with our example demand of 305 gpm, would you go with a 300 or 400 gpm rated fire pump?