Skip to main content

Seismic design changes - 2012 IBC

DesignMaps Application and 2008 Design Data
USGS has released an updated DesignMaps application which is a great application.  However, before you start applying it to 2009 International Building Code please make sure to read their FAQ page which states:
This application should currently only be used to investigate which design values will likely be mandated in the future.

This recommendation by USGS is based on the hierarchy of the codes and standards, which is as follows:
2003 IBC2006 IBC2009 IBC2012 IBC
ASCE7-02ASCE7-05ASCE7-05ASCE7-10
USGS 2002USGS 2002USGS 2002USGS 2008

The DesignMaps application utilizes information from the 2008 USGS National Seismic Hazard Maps information.   For 2008 the hazard values in the Central and Eastern U.S. have been reduced by 10-25% in many cases, and most 1-second period ground motion values for the Western U.S. have also been reduced, in some cases by as much as 30%.

Example differences between 2002 and 2008 Design Data
Lets look at a comparison of several values based on the 2002 vs 2008 hazard values.  (Examples based  Site Class 'D' and Occupancy Category of 'II').
Atlanta, GA (Lat 33.7489954, Lng -84.3879824)
Data SourceSsS1SdsSd1Sds Design CatSd1 Design Cat
2002 Design Data0.2260.0850.2410.137BC
2008 Design Data0.1850.0900.1970.144BC

Sacramento, CA (Lat 38.5815719, Lng -121.4943996)
Data SourceSsS1SdsSd1Sds Design CatSd1 Design Cat
2002 Design Data0.5910.2440.5230.311DD
2008 Design Data0.6750.2940.5670.355DD

Casper, WY (Lat 42.866632, Lng -106.313081)
Data SourceSsS1SdsSd1Sds Design CatSd1 Design Cat
2002 Design Data0.3700.0770.3710.123CB
2008 Design Data0.2770.0740.2910.118BB
As seen in the last example for Casper, Wyoming, seismic bracing for fire sprinkler piping is not required based on which design criteria is applied.  The Sds value is 21% less in the 2008 values.  So whether you utilize the 2002 or 2008 hazard data can make a significant difference on your project.

Anvil Fire's Seismic Force Calculation App provides values based on the 2002 hazard values published by USGS and is basically identical to the Java Ground Motion Parameter Calculator provided by USGS.  Consult with your AHJ, but at this time we recommend that you follow USGS's recommendation to only use the DesignMaps application to investigate the requirements of the future 2012 International Building Code.

For more detailed information on how to determine the seismic design forces for fire suppression systems, please read our blog post on Seismic Design For Fire Sprinkler Systems.

Popular posts from this blog

Installation of Diesel Fuel Tanks for Fire Pumps (OLD)

This article is based upon 2009 IFC codes and is obsolete. See newer version here:  https://blog.anvil-fire.com/2024/03/installation-of-diesel-fuel-tanks-for.html After you have determined the size of fuel tank you need for a diesel fire pump, what are the general requirements for installation?  Assuming that you are under under the International Building/Fire Codes, you would go through the following chain of code references: IFC (2009 edition) 3401.2 Nonapplicability. This chapter shall not apply to liquids as otherwise provided in other laws or regulations or chapters of this code, including: ... (3) Storage and use of fuel oil in tanks and containers connected to oil-burning equipment. Such storage and use shall be in accordance with Section 603 . For abandonment of fuel oil tanks, this chapter applies. IFC (2009 edition) 603.1 Installation. The installation of nonportable fuel gas appliances and systems shall comply the International Fuel Gas Code. The installation of all oth

Diesel Exhaust Requirements

The exhaust from a diesel engine driving a fire pump is an often-overlooked item.  The high heat put out by the exhaust is a hazard to occupants and can greatly contribute to overheating the room itself. NFPA 20 (2013 edition), section 11.5 covers "Engine Exhaust" and should be carefully reviewed. However as a starting point, the following items should be considered. Exhaust Discharge Location The first step is to determine where you are going to discharge the exhaust gases. NFPA 20 section 11.5.3 for "exhaust discharge location" has the generic common-sense requirements of do not discharge where you might hurt people, damage the building, or directed on combustible materials. But very little specific requirements are provided. There is a loose reference in NFPA 20 back to NFPA 37 ( Standard for the Installation and Use of Stationary Combustion Engines and Gas Turbines ). In addition, the International Mechanical Code (IMC) section 915.1 directs us back to NFPA 3

Fire Pump Rating (Size) Selection

Fire pump sizing is not like commercial pump sizing. We don't care about efficiency, and you order pumps in only specific sizes. This article touches upon some items to consider when picking a fire pump. In general, the first step is determining your system demand point. Discussion of how exactly you determine this is beyond the scope of this article and has a lot of nuance depending upon your site-specific needs. However, for simplicity let's assume that you have a dry-system in an attic with a demand point of 305 gpm (2535 sq ft x 0.10 gpm/sq ft x 1.20 overflow/imbalance factor). Rated Flow (gpm) Sizing The first item you must specify is the pump flow rate. Per NFPA 20 (2013 edition) table 4.8.2 pumps are only allowed to be listed with the following flow rates in gpm: 25, 50, 100, 150, 200, 250, 300, 400, 450, 500, 750, 1000, 1250, 1500, 2000, 2500, 3000, 3500, 4000, 4500, 5000 So with our example demand of 305 gpm, would you go with a 300 or 400 gpm rated fire pump?