Skip to main content

Diesel Engine Cooling Loops

Photo of Clarke Fire cooling loop name plate
Make sure you are in compliance with FM Global's requirements for cooling loops on diesel engines. FM Global Approval Standard 1333 was updated in 30 Nov 2013, but compliance was not required until 1 April 2015.

Clarke Fire has an excellent write-up on their web page that you can find here. But, we wanted to summarize the key requirements.


    Photo of new Clarke Fire cooling loop sensor locations
  • FM Approval - Cooling loops are now required to be approved and therefore they will have the FM logo on a nameplate.
  • Low Raw Water Flow Alarm - This switch is set to activate at 75% of the required flow rate.
  • High Raw Water Temperature Alarm - This switch is set at 105F (40C).

Popular posts from this blog

Installation of Diesel Fuel Tanks for Fire Pumps (OLD)

This article is based upon 2009 IFC codes and is obsolete. See newer version here:  https://blog.anvil-fire.com/2024/03/installation-of-diesel-fuel-tanks-for.html After you have determined the size of fuel tank you need for a diesel fire pump, what are the general requirements for installation?  Assuming that you are under under the International Building/Fire Codes, you would go through the following chain of code references: IFC (2009 edition) 3401.2 Nonapplicability. This chapter shall not apply to liquids as otherwise provided in other laws or regulations or chapters of this code, including: ... (3) Storage and use of fuel oil in tanks and containers connected to oil-burning equipment. Such storage and use shall be in accordance with Section 603 . For abandonment of fuel oil tanks, this chapter applies. IFC (2009 edition) 603.1 Installation. The installation of nonportable fuel gas appliances and systems shall comply the International Fuel Gas Code. The installation of all oth

Diesel Exhaust Requirements

The exhaust from a diesel engine driving a fire pump is an often-overlooked item.  The high heat put out by the exhaust is a hazard to occupants and can greatly contribute to overheating the room itself. NFPA 20 (2013 edition), section 11.5 covers "Engine Exhaust" and should be carefully reviewed. However as a starting point, the following items should be considered. Exhaust Discharge Location The first step is to determine where you are going to discharge the exhaust gases. NFPA 20 section 11.5.3 for "exhaust discharge location" has the generic common-sense requirements of do not discharge where you might hurt people, damage the building, or directed on combustible materials. But very little specific requirements are provided. There is a loose reference in NFPA 20 back to NFPA 37 ( Standard for the Installation and Use of Stationary Combustion Engines and Gas Turbines ). In addition, the International Mechanical Code (IMC) section 915.1 directs us back to NFPA 3

Fire Pump Rating (Size) Selection

Fire pump sizing is not like commercial pump sizing. We don't care about efficiency, and you order pumps in only specific sizes. This article touches upon some items to consider when picking a fire pump. In general, the first step is determining your system demand point. Discussion of how exactly you determine this is beyond the scope of this article and has a lot of nuance depending upon your site-specific needs. However, for simplicity let's assume that you have a dry-system in an attic with a demand point of 305 gpm (2535 sq ft x 0.10 gpm/sq ft x 1.20 overflow/imbalance factor). Rated Flow (gpm) Sizing The first item you must specify is the pump flow rate. Per NFPA 20 (2013 edition) table 4.8.2 pumps are only allowed to be listed with the following flow rates in gpm: 25, 50, 100, 150, 200, 250, 300, 400, 450, 500, 750, 1000, 1250, 1500, 2000, 2500, 3000, 3500, 4000, 4500, 5000 So with our example demand of 305 gpm, would you go with a 300 or 400 gpm rated fire pump?