Skip to main content

Seismic Design For Fire Sprinkler Systems - Part 2

Continued from Part 1 of seismic design for fire sprinkler systems.

After you have determined if you need seismic bracing, how do you determine the amount of Horizontal Seismic Force or Fp to apply?  (Hint - You can just go to our Seismic Calculator App and have much of the look up work done for you.)

STEP ONE - APPLICABLE STANDARDS AND CODES
Assuming that you are working in a jurisdiction that has adopted the International Building Code (IBC), you would start with section 1613.1 which states:
1613.1 Scope. Every structure, and portion thereof, including
nonstructural components that are permanently attached to
structures and their supports and attachments, shall be
designed and constructed to resist the effects of earthquake
motions in accordance with ASCE 7, excluding Chapter 14 and
Appendix l1A. The seismic design category for a structure is
permitted to be determined in accordance with Section 1613
 or
ASCE 7.
 Furthermore the International Mechanical Code (IMC) section 301.15 states:
301.15 Seismic resistance. When earthquake loads are applicable in accordance with the International Building Code, mechanical system supports shall be designed and installed for the seismic forces in accordance with the International Building Code.
Looking in the appendix of the 2009 edition of IBC (page 590), we can see that the 2005 edition of ASCE 07 or ASCE 07-05 is adopted.  So what is ASCE 07-05?  The name of the standard is "Minimum Design Loads for Buildings and Other Structures" and is published by the American Society of Civil Engineers (ASCE).


STEP TWO - DETERMINE THE FORCE FACTOR
ASCE 07-05 paragraph 13.3.1 is the applicable section for "nonstructural" components and provides the following formula for determining the horizontal design force (Fp) to be applied:
ASCE Formula
Most of the variables are already defined by NFPA 13 and/or ASCE 07-05 as follows:

Variable
Standard Value
Definition
ap
2.5
Component amplification factor from Table 13.6-1 (Seismic Coefficients for Mechanical and Electrical Components) – “Piping and tubing not in accordance with ASME B31, including in-line components, constructed of high or limited deformability materials, with joints made by threading, bonding, compression couplings, or grooved couplings”.
(Note the 2002 edition of ASCE 7 recommended ap = 1.0)
Rp
4.5
Component response modification factor from Table 13.6.-1 (same item as ap above)
(Note the NFPA 13 2002 TIA 02-1 recommended a Rp = 3.5)
Ip
1.5
Component Importance factor (Ip) per ASCE 7-05 13.1.3 “… The component importance factor, Ip, shall be taken as 1.5 if any of the following conditions apply: 1. The component is required to function for life-safety purposes after an earthquake, including fire protection sprinkler systems…”
(Note the NFPA 13 2002 TIA 02-1 recommended a Ip = 1.5)
z
-
Height in structure of point of attachment of component with respect to the base.  For items at or below the base, z shall be taken as 0.  The value of z/h need not exceed 1.0.
h
-
Average roof height of structure with respect to base.

As you can see the only missing pieces are the Height of Attachment (z), Height of Structure (h), and Five-percent damped design spectral response acceleration at short periods (Sds).

The calculated design force can be reduced by a factor of 1.4 because ASCE/SEI 7 is based on strength design, whereas NFPA 13 uses allowable stress design. Prior to the 2007 edition, all loads in NFPA 13 were at allowable stress levels with the exception of the buckling loads for brace members. In the 2007 edition, tables that contained the allowable loads on braces have been reduced to add a factor of safety appropriate to the use of allowable stress design



Popular posts from this blog

Installation of Diesel Fuel Tanks for Fire Pumps (OLD)

This article is based upon 2009 IFC codes and is obsolete. See newer version here:  https://blog.anvil-fire.com/2024/03/installation-of-diesel-fuel-tanks-for.html After you have determined the size of fuel tank you need for a diesel fire pump, what are the general requirements for installation?  Assuming that you are under under the International Building/Fire Codes, you would go through the following chain of code references: IFC (2009 edition) 3401.2 Nonapplicability. This chapter shall not apply to liquids as otherwise provided in other laws or regulations or chapters of this code, including: ... (3) Storage and use of fuel oil in tanks and containers connected to oil-burning equipment. Such storage and use shall be in accordance with Section 603 . For abandonment of fuel oil tanks, this chapter applies. IFC (2009 edition) 603.1 Installation. The installation of nonportable fuel gas appliances and systems shall comply the International Fuel Gas Code. The installation of all oth

Diesel Exhaust Requirements

The exhaust from a diesel engine driving a fire pump is an often-overlooked item.  The high heat put out by the exhaust is a hazard to occupants and can greatly contribute to overheating the room itself. NFPA 20 (2013 edition), section 11.5 covers "Engine Exhaust" and should be carefully reviewed. However as a starting point, the following items should be considered. Exhaust Discharge Location The first step is to determine where you are going to discharge the exhaust gases. NFPA 20 section 11.5.3 for "exhaust discharge location" has the generic common-sense requirements of do not discharge where you might hurt people, damage the building, or directed on combustible materials. But very little specific requirements are provided. There is a loose reference in NFPA 20 back to NFPA 37 ( Standard for the Installation and Use of Stationary Combustion Engines and Gas Turbines ). In addition, the International Mechanical Code (IMC) section 915.1 directs us back to NFPA 3

Fire Pump Rating (Size) Selection

Fire pump sizing is not like commercial pump sizing. We don't care about efficiency, and you order pumps in only specific sizes. This article touches upon some items to consider when picking a fire pump. In general, the first step is determining your system demand point. Discussion of how exactly you determine this is beyond the scope of this article and has a lot of nuance depending upon your site-specific needs. However, for simplicity let's assume that you have a dry-system in an attic with a demand point of 305 gpm (2535 sq ft x 0.10 gpm/sq ft x 1.20 overflow/imbalance factor). Rated Flow (gpm) Sizing The first item you must specify is the pump flow rate. Per NFPA 20 (2013 edition) table 4.8.2 pumps are only allowed to be listed with the following flow rates in gpm: 25, 50, 100, 150, 200, 250, 300, 400, 450, 500, 750, 1000, 1250, 1500, 2000, 2500, 3000, 3500, 4000, 4500, 5000 So with our example demand of 305 gpm, would you go with a 300 or 400 gpm rated fire pump?